Industry News

Principle of Fluxgate Current Sensors | Analysis of AC/DC Composite Current Sampling Technology

In the design of power conversion and electrical energy acquisition projects, the zero-point stability of current sampling, the degree of signal linearity, and low-frequency errors directly affect the control performance of the equipment and the reliability of the acquired data. Conventional current transformers can only measure AC; standard Hall-effect current sensors, under conditions of small DC currents and significant temperature variations, struggle to maintain stable zero-point drift and temperature compensation. Fluxgate current sensors, operating on the principle of magnetic modulation, can achieve high-precision current measurement for DC, low-frequency AC, and mixed AC/DC waveforms, making them a commonly used type of sensing device in power equipment.

800.jpg

I. Principle of the Fluxgate Current Sensor

To understand the principles of the fluxgate current sensor , the key is to grasp the working logic behind the core’s periodic magnetic saturation and the closed-loop zero-flux operation.

The fluxgate sensor core consists of a high-permeability soft magnetic alloy core (such as permalloy or nanocrystalline) and multiple sets of coils, including an excitation coil, a signal-sensing coil, and a compensation coil.

The excitation circuit continuously outputs a high-frequency alternating signal, driving the magnetic core to repeatedly magnetize back and forth between the positive and negative saturation regions.

1. When there is no external magnetic field (no measured current), the core’s forward and reverse magnetization processes are symmetrical, and the secondary harmonic signal detected by the pickup coil is nearly 0;

2. When the current under test generates an external magnetic field, it disrupts the equilibrium of the core’s magnetization, causing the pickup coil to detect a second-harmonic signal whose strength is proportional to the magnitude of the external magnetic field. Simply put: the external current alters the timing sequence of the core’s saturation, and by demodulating this signal, the circuit can determine the magnitude of the current being measured.

Nowadays, most industries use a closed-loop zero-flux structure. After processing the acquired signal, the circuit drives the compensation coil to generate an opposing magnetic field, which cancels the magnetic field produced by the measured current in the core, keeping the internal magnetic field of the core close to zero.

In this state, the magnetic core operates in its linear region, thereby suppressing errors caused by hysteresis, nonlinearity, and temperature variations. Based on the magnetomotive force balance, the measured current waveform can be reconstructed by sampling the voltage across the compensation loop resistor, while simultaneously achieving galvanic isolation between high- and low-voltage circuits.

Supplement: Open-loop fluxgate sensors have a simple structure, but their temperature drift and long-term stability are typically moderate; for industrial acquisition applications with stringent requirements, closed-loop zero-flux schemes are generally preferred.

Wuxi nGV, leveraging its proprietary magnetic modulation zero-flux technology, has launched a full range of fluxgate current sensors, spanning metrology-grade, measurement-grade, and industrial-control-grade product lines. These sensors can accommodate diverse measurement requirements, from small signals to large currents, while delivering low temperature drift, minimal zero-drift, and excellent anti-interference performance. They provide sampling solutions for precision measurement applications such as energy storage, photovoltaics, AIDC computing power supplies, and laboratory metrology.

II. Actual Performance of the Fluxgate Current Sensor in AC and DC Measurements

1. DC and Low-Frequency Signal Acquisition

Current transformers rely on alternating magnetic field induction and cannot measure direct current. Although Hall sensors can measure DC, in low-current scenarios, their zero-point drifts with time and temperature, and prolonged data integration can easily accumulate errors, making them unsuitable for applications such as battery state estimation, leakage current monitoring, and power calibration.

fluxgate current sensors are highly sensitive to static magnetic fields and can measure DC, steady currents, as well as extremely slow-changing currents with frequencies approaching 0Hz. The closed-loop architecture ensures zero-point stability, making them suitable for acquiring small DC currents and weak leakage currents. During long-term measurements, they exhibit reduced error accumulation and are commonly used in energy storage battery packs, power analyzers, DC bus monitoring, standard signal sources, and other devices.

Engineering Tip: Fluxgate sensors are sensitive to static magnetic fields. If the ambient stray magnetic field at the site is strong, magnetic shielding and optimized magnetic circuits should be employed to reduce interference. Wuxi nGV fluxgate products feature a proprietary magnetic shielding design, enhancing measurement stability in complex electromagnetic environments.

2. AC and mixed waveform acquisition

The fluxgate itself performs well in acquiring low-frequency AC signals, but a pure fluxgate solution has limited high-frequency measurement bandwidth.

In the industry, there is a composite magnetic circuit solution that integrates a fluxgate sensor with a current transformer: low-frequency signals are acquired by the fluxgate, while medium- and high-frequency AC signals are handled by the current transformer. The two signal paths are combined for output, providing a bandwidth that spans from DC up to several hundred kHz. This approach can accurately reconstruct superimposed AC–DC waveforms, pulse currents, and PWM ripple, making it well-suited for power circuits—such as photovoltaic inverters, energy storage PCSs, AIDC power supplies, and silicon‑carbide power devices—that feature a DC bias with superimposed high-frequency ripple.

• Waveform acquisition: It can simultaneously acquire AC-DC superimposed current, unidirectional pulse current, and asymmetric alternating current—capabilities that ordinary current transformers cannot achieve;

• Bandwidth characteristics: Pure fluxgate sensors have limited high-frequency capability; composite magnetic circuits broaden the bandwidth, but their magnetic and circuit designs become more complex;

• Phase characteristics: Within the rated operating bandwidth, the signal phase shift is controllable, making it suitable for power calculation and energy measurement.

3. Key considerations when selecting a model

Each current-sampling technique has its own applicable range; when selecting a model, perform a comprehensive evaluation:

1. Compared with Hall sensors, fluxgate sensors require excitation, signal demodulation, and closed-loop feedback circuits, resulting in a more complex circuit structure, higher power consumption, and typically larger dimensions;

2. Core material, shielding structure, PCB routing, and grounding design all affect noise and temperature drift; high-quality, reliable fluxgate products incorporate temperature compensation schemes to enhance performance across a wide temperature range.

3. More suitable for high-precision scenarios that prioritize sampling stability and zero-point performance and require DC measurement; if you only need to measure high-frequency, large currents and are cost-sensitive, Hall sensors and current transformers remain appropriate choices.

III. Typical Application Scenarios

• Energy storage converter PCS, battery BMS DC current acquisition, battery leakage monitoring

• Photovoltaic inverter, AIDC computing power supply power sampling and efficiency testing

• Power analyzers, calibration sources, laboratory metrology equipment

• Current monitoring for rail transit and new energy high-voltage systems

• High-demand power measurement and control scenarios such as scientific research special-purpose power supplies

The Wuxi nGV fluxgate current sensor series can cover the aforementioned scenarios, offering a wide range of measurement ranges and aperture sizes to choose from. It supports electrical isolation between primary and secondary sides and is compatible with on-site busbar and copper bar installation requirements, meeting the needs of equipment R&D, production line testing, laboratory metrology, and other diverse operating conditions.

IV. Selection Reference

If the device needs to simultaneously acquire both DC components and AC ripple, and has stringent requirements for zero-drift, linearity, and long-term stability, a fluxgate current sensor solution can be evaluated. Understanding the operating principle of a fluxgate current sensor helps engineers quickly determine whether the device is suitable for the project.

It addresses the limitations of current transformers, which cannot measure DC, and the tendency of conventional Hall sensors to experience zero-point drift under low-current and wide-temperature conditions. In mixed AC/DC power circuits, the composite magnetic circuit fluxgate sensor can restore the true current waveform, providing reliable raw sampling data for equipment control, energy measurement, and fault diagnosis.

During the project proposal selection phase, you can learn about Wuxi nGV’s full range of fluxgate current sensors and, by considering the project’s measurement range, bandwidth, and accuracy requirements, evaluate the appropriate model.